Permit: T09CM01295

Parcel: 10503032C


Addresses:

5061 N ORACLE RD

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
01/11/2010 MECHANICAL - FINAL Approved IVRS - Inspection :*
1) TESTED DUCT SMOKE DETECTORS
2) CORRECTIONS HAVE BEEN MADE
01/08/2010 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
07/14/2009 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) TERMINATE CONDENSATE DRAINS TO AN APPROVED LOCATION, NOT ON PAVEMENT
2) CANNOT CONFIRM R8 INSULATION
3) 2 NEW UNITS MISSING OUTSIDE AIR INTAKES
4) NEED TO TEST DUCT SMOKE DETECTORS
05/27/2009 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
05/26/2009 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. CONDENSATE PIPING CANNOT TERMINATE AT WASTE VENT
2. ALL LOW VOLTAGE WIRING EXPOSED TO WEATHER MUST BE PROTECTED IN CONDUIT
3. PROVIDE SEDIMENT TRAPS ON GAS PIPING TO UNITS
4. GAS FLEX NOT TO EXCEED 36"
5. PROVIDE R-8 INSULATION ON ALL EXTERIOR DUCTS
6. FLUE EXHAUST MUST BE 10' AWAY OR 3' ABOVE ALL UNIT INTAKES
7. ALL RTU's TO HAVE OUTSIDE AIR INLETS
8. PROVIDE DUCT SMOKE DETECTOR TEST ON UNITS WITH CFM EXCEEDING 2000
9. AUDIO AND VISIBLE ALARMS MUST BE TIED TO DUCT SMOKE DETECTORS