Permit: T09CM01281

Parcel: 12109006A

Inspection Status: Partial Approval

Inspection History: PLUMBING - ROUGH, SOIL

Date Description Inspector Results Comments
04/28/2010 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
1) KITCHEN AREA SOIL PIPING OK, RECALL FOR FD AND FS CONNECTIONS, WRAPS IN PLACE
2) PERM CAP ANY ABANDONED DRAINS THAT ARE STILL CONNECTED TO SANITARY BLDG DRAIN
04/27/2010 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) BACK PITCH AT WATER CLOSET DRAIN
2) GW HAS BACK PITCH AND FLAT SECTION
3) VENT TAKE OFF AT FD NOT INSTALLED AT MIN 45 DEGREE, TRY A WYE WITH A 1/16" BEND AND SWEEP
4) WILL NEED TO RETEST UNDERGROUND AT TIME OF INTERMEDIATE INSPECTION OR INSTALL ABOVE FLOOR TEST TEES NOW
04/22/2010 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PROVIDE AN APPROVED DRAINAGE FITTING FOR TEST TEE
2) PROVIDE 1/4" PER FOOT SLOPE
3) ALL FIXTURES VENTS SHALL RISE VERTICALLY ABOVE FLOW LINE
4) FD CONNECTS TO GW
5) FS AT 3 COMP CONNECTS TO SANITARY 4" UPPER TERMINAL CLEANOUT REQUIRES
04/06/2010 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :*
HAMMER ARRESTORS REQUIRED
REMOVE EXCESS FLEX FROM SOLDIER JOINTS, OK TO INSULATE PER PLAN SPECS.
INSULATE ALL COPPER TOUCHING MSTAL
2" CW SPECIFIED ON PLAN TO FIRST BRANCH. ALSO RPOVIDE 1 1/2 C THRU FLUSHOMETER BRANCH BEFORE REDUCING.
RELINE CHANGE OF LOCATION OF P-3 FIXTURES
SECURE LAV CARRIERS.
03/10/2010 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
1) BELOW SLAB PIPING OK FOR CONCRETE
2) WILL INSPECT PIPING IN CRAWL SPACE WHEN IT IS READY, I.E. SUPPORTS
3) DWV TEST OK PENDING CRAW SPACE INSPECTION
02/12/2010 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PLEASE POST ADDRESS
2) A DRAIN MAY NOT CONNECT TO A VENT
02/11/2010 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :*
PLANS & PERMITS REQUIRED TO BE POSTED AT ALL TIMES.
USE CAR?? TO KEEP SEWER PIPING CAPPED OR PLUGGED