Permit: T09CM01268

Parcel: 141340300

Inspection Status: Approved

Inspection History: EXT METAL CLIPS/EXT SHEATHING

Permit Number - T09CM01268

Inspection Description - EXT METAL CLIPS/EXT SHEATHING

Inspection Status - Approved

Date Description Inspector Results Comments
07/28/2009 EXT METAL CLIPS/EXT SHEATHING Approved IVRS - Inspection :*
07/16/2009 EXT METAL CLIPS/EXT SHEATHING Partial Approval IVRS - Inspection :*
1) OK TO COVER WALLS (BCI/TJI SWITCH FROM PLAN) GET OK'D
2) ARE B.C.I. 5,000 EQUAL TO TJI 560?
07/09/2009 EXT METAL CLIPS/EXT SHEATHING Not ready for Inspection IVRS - Inspection :*
1) ADD 2ND STUD TO END OF WALL GARAGE SHEAR THAT WAS MISSED SOUTH WALL, NAIL TO SHEATHING
2) VERTICAL NAILING TO ALL STUDS CONNECTED TO P.A. OR H.D.
3) RAT RUN TO GO ON WEB NOT CHORD (SEE TRUSS SPECS)
4) TJI ITEM ? YOU INSTALLED A BCI 67/8, 2" CHORD
07/06/2009 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) A02 TRUSS NEEDS SHIM
2) MISSED #5 SHEARWALL AT GARAGE
3) NAIL BOTH STUDS AT EACH H.D. OR P.A.
4) RAT RUNS ON SOUTHSIDE
5) MISSING NAILING ON ROOF/REMOVE CRICKET AT GARAGE TO HOUSE
6) CHECK ON SIZE OF T.J.I.'S FOR GARAGE
7) FLOOR RECEPT CONDUIT AT SLIDER KING STUD