Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/25/2010 | MECHANICAL - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 03/19/2010 | MECHANICAL - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) COATING THE EXTERIOR OF PVC WITH PRIMER AFTER THE JOINTS ARE MADE UP IS NOT ACCEPTABLE 2) JOINTS ARE TO BE CUT ON AND PROPERLY PRIMED 3) ANY FURTHER FAILED INSPECTIONS WILL BE REFEE ASSESSED |
|
| 03/17/2010 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) ALL PVC TO BE PRIMED, ALL PRIMER TO BE PURPLE IN COLOR PER U.P.C. |
|
| 03/16/2010 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) FOAM INSULATION ON LINE SETS IS DAMAGED, REPAIR OR REPLACE |