Permit: T09CM01258

Parcel: 117141070


Addresses:

58 W CUSHING ST


Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Permit Number - T09CM01258

Inspection Description - MECHANICAL - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
03/25/2010 MECHANICAL - INTERMEDIATE Approved IVRS - Inspection :*
03/19/2010 MECHANICAL - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) COATING THE EXTERIOR OF PVC WITH PRIMER AFTER THE JOINTS ARE MADE UP IS NOT ACCEPTABLE
2) JOINTS ARE TO BE CUT ON AND PROPERLY PRIMED
3) ANY FURTHER FAILED INSPECTIONS WILL BE REFEE ASSESSED
03/17/2010 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) ALL PVC TO BE PRIMED, ALL PRIMER TO BE PURPLE IN COLOR PER U.P.C.
03/16/2010 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) FOAM INSULATION ON LINE SETS IS DAMAGED, REPAIR OR REPLACE