Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T09CM01258
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/27/2010 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* 1) CHECKED WITH MECHANICAL INSPECTOR-UNIT HAS INTERIOR DISCONNECT PLUG |
|
07/23/2010 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) FINISH #2 PREVIOUS INSPECTION |
|
07/15/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : There is no access to the site.| 920* |
|
07/09/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) BOXES MORE THAN 1/4" BOX TO SURFACE 314.20 USE APPROVED ARC SHIELD 2) PLEASE VERIFY DISCONNECTING MEANS FOR A/C UNIT 3) PROVIDE LADDER TO OPEN AND INSPECT OUTSIDE LIGHT BOX AND FOR ROOF ACCESS 4) BREAKERS TO BE LISTED FOR USE BY MANUFACTURE |