Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T09CM01258
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/27/2010 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
03/15/2010 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) CONNECTOR AT BOX 2) OK WALLS AND LID |
|
03/12/2010 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) PROVIDE CONNECTOR FOR CABLE ENTERING BOX 312.5 (C) |
|
03/10/2010 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) BOX NEEDED FOR LIGHT 300.15 AND 110.3 (?) |
|
03/05/2010 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : 1. EXTERIOR LIGHT NEEDS A BOX 2. USE APPROVED SPLICE CONNECTOR FOR GROUNDS 3. USE APPROVED EXTENSION BOXES |
|
12/07/2009 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) SUPPORT AND SECURE NM CABLE PER CODE (CANS & BOXES) 2) MAKE UP DEVICE BOXES TO INSPECT 3) PROTECT NM CABLE FROM SHARP METAL EDGES 4) WHERE IS EXTERIOR LIGHT 5) EXTEND EXISTING RECEPT TO SURFACE 6) DOES THIS ROOM NEED TO MEET THE REQUIREMENTS OF 517.13 ? |