Permit: T09CM01258

Parcel: 117141070


Addresses:

58 W CUSHING ST


Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T09CM01258

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
07/27/2010 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
03/15/2010 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) CONNECTOR AT BOX
2) OK WALLS AND LID
03/12/2010 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) PROVIDE CONNECTOR FOR CABLE ENTERING BOX 312.5 (C)
03/10/2010 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) BOX NEEDED FOR LIGHT 300.15 AND 110.3 (?)
03/05/2010 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
1. EXTERIOR LIGHT NEEDS A BOX
2. USE APPROVED SPLICE CONNECTOR FOR GROUNDS
3. USE APPROVED EXTENSION BOXES
12/07/2009 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) SUPPORT AND SECURE NM CABLE PER CODE (CANS & BOXES)
2) MAKE UP DEVICE BOXES TO INSPECT
3) PROTECT NM CABLE FROM SHARP METAL EDGES
4) WHERE IS EXTERIOR LIGHT
5) EXTEND EXISTING RECEPT TO SURFACE
6) DOES THIS ROOM NEED TO MEET THE REQUIREMENTS OF 517.13 ?