Inspection Status: Approved
Inspection History: FIRE SPKLR - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/13/2015 | FIRE SPKLR - FINAL | Approved | ||
| 07/10/2015 | FIRE SPKLR - FINAL | Partial Approval | Need escutcheon plates shut off to water services is before the fire sprinkler riser (originally installed in 1999 or 2000). Water can be turned off to the fire sprinkler system and needs to be re plumbed so that there is no shut off between water supply from domestic and the riser ( should come after the fire riser check valve). |