Permit: T09CM01245

Parcel: 13632002T

Inspection Status: Approved

Inspection History: FIRE SPKLR - FINAL

Date Description Inspector Results Comments
07/13/2015 FIRE SPKLR - FINAL Approved
07/10/2015 FIRE SPKLR - FINAL Partial Approval Need escutcheon plates
shut off to water services is before the fire sprinkler riser (originally installed in 1999 or 2000).
Water can be turned off to the fire sprinkler system and needs to be re plumbed so that there is no shut off between water supply from domestic and the riser ( should come after the fire riser check valve).