Permit: T09CM01232

Parcel: 12801005H

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T09CM01232

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
08/06/2009 ELECTRIC - FINAL Approved
08/05/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) STRAP SEAL TIGHT WITHIN 12" OF CONNECTIONS NEED TO BE STRAPPED EVERY 54" IN BETWEEN
2) CANNOT USE FLEXIBLE CORD AS PERMANENT WIRING METHOD
3) NEED MINIMUM 12 GAUGE WIRE ON 20 AMP CIRCUIT
4) SEAL RACEWAYS INTO COOLERS
5) GROUND METAL BOXES
6) BOXES TO BE PROPERLY SECURED
7) HAVE QUALIFIED ELECTRICAL CONTRACTOR MAKE CORRECTIONS AND CHECK ELECTRICAL WIRING TO COOLERS
08/03/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) ALL PREVIOUS ITEMS CORRECTED
2) NEED TO FINISH WIRING FOR WALK IN COOLERS
07/31/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) DISCONNECTS TO BE GROUNDED. INSTALL BONDING SCREW
2) NEED MINIMUM 6" OF FREE CONDUCTOR LENGTH
3) RECEPTACLES WITH NO POWER
4) NEED MINIMUM 2 SCREWS TO MOUNT RECEPTS IN INDUSTRIAL COVERS
5) HAVE OPEN JUNCTION BOX ABOVE CEILING
6) CLOSE OPEN GUTTER
7) STRAP SEAL TIGHT AND METAL FLEX PER CODE
8) CANNOT ACCESS WALK INS, TILE BEING INSTALLED
9) FINISH WIRING WALK INS
10) INSTALL SERVICE RECEPTACLE FOR A/C UNIT ON ROOF