Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T09CM01223
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/01/2009 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
09/28/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) SEE NOTE #2 INSPECTION 8/19/09 ALSO GROUND BOXES 2) OK COPY ROOM, NEW SECTION WALLS AND CEILINGS, EXCEPT OUTSIDE WALL, LIGHTING HAS NO CONNECTORS |
|
09/23/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) NOT READY INSPECTIONS WILL RESULT IN REINSPECTION FEES. CHECK WITH ELECTRICIAN PRIOR TO SCHEDULING INSPECTIONS 2) OK WALLS 2ND FLOOR 3) OK CEILINGS 2ND FLOOR |
|
08/19/2009 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) SUPPORT CABLING BELOW PANEL ALSO CONDUIT PER CODE-THIS INCLUDES TELE/DATA LV CABLING IN WALLS PER 334-725-800 NEC 2) USE APPROVED CONNECTORS IN METAL BOXES, PLASTIC BUSHING NOT APPROVED. ONLY IF CLAMP TYPE |
|
08/14/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) UNDER GROUND RIBBED RED 2 1/2 RACEWAY FROM 627 N. 6TH TO POWER POLE, THEN FROM POWER POLE TO 607 TRENCH OK |