Inspection History: REINFORCED MASONRY PRE-GROUT

Permit Number - T09CM01223

Inspection Description - REINFORCED MASONRY PRE-GROUT

Inspection Status - Approved

Date Description Inspector Results Comments
10/28/2009 REINFORCED MASONRY PRE-GROUT Approved IVRS - Inspection :*
08/06/2009 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
1) TOP OUT ON COLUMNS AND NORTHWEST
08/04/2009 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
1) 12'-16' LIFT OK
07/31/2009 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
1) PERIMETER WALLS AT 8'-11' 4"; COLUMNS AT 8'-12' LINTELS IN PLACE ABOVE OPENINGS; LEDGER BOLTS IN PLACE-OK TO GROUT PROGRESS AREAS
07/28/2009 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
1) COLUMNS AND WALLS (PERIMETER) AT 4'-8' AFFE-OK TO GROUT PROGRESS AREAS
07/24/2009 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
1) CMU MASONRY WALL REINFORCEMENT FOR ROOMS #106,107,107A AND 108 FROM ? TO 4"-OK TO GROUT
07/23/2009 REINFORCED MASONRY PRE-GROUT Not ready for Inspection IVRS - Inspection :*
1) PER PLAN DETAIL SEE GSN FOR COLUMN TIE IN COULD NOT FIND ANY 6 ON S-3
2) NEED REBAR MINIUM LAP SCHEDULE
3) NEED HEIGHTS FOR BOND BM5 DETAIL 1/S-3