Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
Permit Number - T09CM01206
Inspection Description - MECHANICAL - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/22/2009 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* | |
12/17/2009 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) INSULATE SPIRAL DUCT ABOVE CONFRENECE ROOM 2) PROVIDE BEADED COLLARS AT ALL FLEX DUCT CONNECTIONS 3) OTHER ITEMS ON LIST OK 4) ROUND DUCTS OK AS PER ENGINEER LETTER 5) OK PARTIAL TILES |
|
12/16/2009 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
12/14/2009 | MECHANICAL - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* 1) PROVIDE LETTER REFERENCED 11-10-09 2) PROVIDE BEADED COLLARS PER MANUF INSTALL INSTRUCTIONS. 3) PROVIDE SEISMIL SUPPORTS 4) CONNECT FLEX USING PANDULT STRAP & TAPE PER DETAIL (3) M3.1 |
|
11/13/2009 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) OK TO PROCEED |
|
11/10/2009 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) SEAL ALL DUCT AND TAPS IN HARD LID AREA 2) PROVIDE ENGINEERS APPROVAL ON ALL CHANGES TO PLANS AND SPECS (ROUND DUCT ON EXHAUST, FLEX-DUCT ON EXHAUST) DOVE TAIL COLLARS |
|
10/23/2009 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* SUSPENDED ROUGH DUCT OK TO INSULATE CONFIRMED AIR SCOOP SPIN IN COLLARS WERE USED. |