Permit: T09CM01206

Parcel: 140260370

Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Permit Number - T09CM01206

Inspection Description - MECHANICAL - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
12/22/2009 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
12/17/2009 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) INSULATE SPIRAL DUCT ABOVE CONFRENECE ROOM
2) PROVIDE BEADED COLLARS AT ALL FLEX DUCT CONNECTIONS
3) OTHER ITEMS ON LIST OK
4) ROUND DUCTS OK AS PER ENGINEER LETTER
5) OK PARTIAL TILES
12/16/2009 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
12/14/2009 MECHANICAL - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
1) PROVIDE LETTER REFERENCED 11-10-09
2) PROVIDE BEADED COLLARS PER MANUF INSTALL INSTRUCTIONS.
3) PROVIDE SEISMIL SUPPORTS
4) CONNECT FLEX USING PANDULT STRAP & TAPE PER DETAIL (3) M3.1
11/13/2009 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) OK TO PROCEED
11/10/2009 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) SEAL ALL DUCT AND TAPS IN HARD LID AREA
2) PROVIDE ENGINEERS APPROVAL ON ALL CHANGES TO PLANS AND SPECS (ROUND DUCT ON EXHAUST, FLEX-DUCT ON EXHAUST) DOVE TAIL COLLARS
10/23/2009 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
SUSPENDED ROUGH DUCT OK TO INSULATE
CONFIRMED AIR SCOOP SPIN IN COLLARS WERE USED.