Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
Permit Number - T09CM01206
Inspection Description - PLUMBING - ROUGH, SOIL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/27/2009 | PLUMBING - ROUGH, SOIL | Approved | IVRS - Inspection :* | |
09/02/2009 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* 1) PROVIDE TEST ON ALL UNDERGROUND PIPING AFTER REPAIR PIPING AND FITTING FOR WATER CLOSET |
|
08/20/2009 | PLUMBING - ROUGH, SOIL | Not ready for Inspection | VENT FOR BLDG SEWER. ABS IS NOT PERMITTED TO BE USED WITH RECTOR SEAL #5 REMOVE AND REPLACE FITTING - USE APPROVED THREAD JOINT COMPOUND. OK TO COVER UNDERGROUNG PORTION OF VENT |
|
08/14/2009 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* 1) WATER TEST THRU BLDG AND BACK WATER VALVE AND DOWN STREAM CLEANOUT TO 6' BLDG EXTERIOR OK 2) WILL NEED RETEST FOR BACK WATER MAIN SEWER VENT |
|
08/13/2009 | PLUMBING - ROUGH, SOIL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SEE NOTE #2 ABOVE POST THIS ADDRESS 2) HAVE PIPING UNDER TEST WHEN CALLING FOR INSPECTION |