Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - PROGRESS
Permit Number - T09CM01206
Inspection Description - ELECTRIC - PROGRESS
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/22/2010 | ELECTRIC - PROGRESS | Approved | IVRS - Inspection :* | |
01/21/2010 | ELECTRIC - PROGRESS | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* GENERATOR: 1) GROUNDING ELECTRODE TO BE CONTINOUS 250.64 2) PROTECT SEAL TITE FROM SHARP METAL EDGES 3) NEED GENERATOR TEST REPORT 4) GENERATOR IS UN-LISTED 5) CANNOT VERIFY TRANSFER SWITCH LISTING 6) SUPPORT PVC CONDUITS BLDG: 1) NEED OUTDOOR LIGHTING VERIFICATION 2) FINISH PREVIOUS INSPECTION 31.420 & 21 AND PANEL DIRECTORIES 408.4 3) PLANS CALL FOR 15' OF CONDUCTOR TO CONTRACTOR PANEL 4) NEED SERIES RATING LABELS |
|
01/19/2010 | ELECTRIC - PROGRESS | Not ready for Inspection | IVRS - Inspection :* 1) CANCELLED |
|
01/07/2010 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* 1) BOXES MORE THAN 1/4" 314.20 2) FINISH RECEPTION DESK 3) MISSING BATHROOM FIXTURE 4) FINISH FLOOR BOXES 5) FILL OUT PANLE DIRECTORIES PER 408.4 6) NEED TO SEE OFFICE FURNITURE CONNECTIONS 7) NOT ALL AREAS ACCESSIBLE ROOF: 1) PROPERLY GROUND, SUPPORT AND PROTECT CONDUCTOR FOR SATELITE DISH 820.15 |
|
12/30/2009 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* | |
12/29/2009 | ELECTRIC - PROGRESS | Not ready for Inspection | IVRS - Inspection :* | |
12/16/2009 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* | |
12/14/2009 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* | |
11/17/2009 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* | |
11/13/2009 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* | |
11/04/2009 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* | |
11/03/2009 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* | |
11/02/2009 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* | |
10/30/2009 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* | |
10/29/2009 | ELECTRIC - PROGRESS | Not ready for Inspection | IVRS - Inspection :* | |
10/28/2009 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* | |
10/27/2009 | ELECTRIC - PROGRESS | Not ready for Inspection | IVRS - Inspection :* 1) CANCELLED BY CONTRACTOR |
|
10/26/2009 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* | |
10/15/2009 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* 1) OK 3 LIGHTS AT ENTRY SOFFIT |
|
10/13/2009 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* | |
09/25/2009 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* | |
09/17/2009 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* | |
09/10/2009 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* | |
09/09/2009 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* | |
09/02/2009 | ELECTRIC - PROGRESS | Not ready for Inspection | IVRS - Inspection :* | |
08/28/2009 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* | |
08/24/2009 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* | |
08/18/2009 | ELECTRIC - PROGRESS | Not ready for Inspection | IVRS - Inspection :* | |
08/17/2009 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* 1) OK BRANCH CIRCUIT PVC CONDUITS-AS MARKED |
|
08/14/2009 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* | |
08/13/2009 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* |