Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - UNDERGROUND
Permit Number - T09CM01206
Inspection Description - ELECTRIC - UNDERGROUND
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/22/2010 | ELECTRIC - UNDERGROUND | Approved | IVRS - Inspection :* | |
10/13/2009 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1) OK UG FOR GATE OPERATOR WEST END 2) OK 1-1" PVC EAST END AT TRAILER 3) OK INSTALL OF WALKER DUCT |
|
09/25/2009 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1) OK PVC CONDUITS AND #4 GROUND TO PARKING STRUCTURE AS MARKED-NOTE: ENCASE LESS THAN 18" 2) CONDUITS TO BE PER 300.5 18" |
|
09/17/2009 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* | |
09/10/2009 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1) OK PVC AS MARKED |
|
09/09/2009 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* | |
09/02/2009 | ELECTRIC - UNDERGROUND | Not ready for Inspection | IVRS - Inspection :* 1) WIRE WAY NOT APPROVED |
|
08/28/2009 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1) OK 24 FLOOR BOXES AND CONDUIT 2) WIRE WAY NOT AS PER PLAN-MODIFICATION ONLY AS PER LISTING ALLOWS |
|
08/24/2009 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1) OK PVC CONDUITS BRANCH CIRCUITS AS MARKED |
|
08/18/2009 | ELECTRIC - UNDERGROUND | Not ready for Inspection | IVRS - Inspection :* | |
08/17/2009 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* | |
08/14/2009 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1) OK PVC AT ELECTRIC ROOM-PRIMARY AND FEEDER SECONDARY AND GENERATOR CONDUITS |
|
08/13/2009 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1) OK 3-3" PVC FROM TEP XFMR STUBBED INTO BLDG 2) INSTALL WORKING RIBBON ABOVE SERVICE RACEWAYS PER NEC 300.5 3) OK 1-2 1/2" PVC AND 1-1" PVC FROM ELECTRIC CLOSET TO JUST OUTSIDE BLDG FOOTING |