Permit: T09CM01205

Parcel: 13707044A


Addresses:

5201 S 12TH AV


Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Permit Number - T09CM01205

Inspection Description - PLUMBING - GAS PRESSURE TEST

Inspection Status - Approved

Date Description Inspector Results Comments
01/10/2012 PLUMBING - GAS PRESSURE TEST Approved PER PL FINAL
03/04/2011 PLUMBING - GAS PRESSURE TEST Partial Approval 2" FROM SOUTHWEST METER THRU ANSUL TO STOVE/OVEN AND 2 POY COOKERS AND EXISTING WATER HEATER WITH 3 VALVED STUBS ON ROOF. GAS CARD LEFT FOR NEEDED TESTING AND CONTINUATION OF WORK WITH MECHANICAL INSPECTOR, TO GIVE OK FOR USE
03/01/2011 PLUMBING - GAS PRESSURE TEST Partial Approval 1. 10PSI TEST FROM NEW METER LOCATION TO C-3, C-4, C-5, WITH 1/2' TO WATER HEATER AND 1 1/4' STUB TO OTHER FIXTURES ON ROOF. 2. PROVIDE SHUT OFF VALVES AS SHOWN ON P-1 AND RETEST 3. VERIFY ANSUL VALVE TO G-3, G-4, G-5, IS OPEN POSITION.
02/14/2011 PLUMBING - GAS PRESSURE TEST Not ready for Inspection IVRS - Inspection :*
09/08/2010 PLUMBING - GAS PRESSURE TEST Partial Approval IVRS - Inspection :*
1) GAS PIPING IN PARKING LOT NOT 18" OF COVER
2) GAS PIPING IS 12" OFF COVER, PROVIDE PROTECTION IN PARKING LOT FOR GAS PIPING
3) GAS PIPING FROM METER TO ROOF ONLY
09/07/2010 PLUMBING - GAS PRESSURE TEST Not ready for Inspection IVRS - Inspection :*
1) PROVIDE TAPE AND PRIMER ON ALL FITTING AND TOOL MARKS
2) PROVIDE 18" OF COVER ON ALL GAS PIPING IN PARKING AREA
3) INSPECTION FOR PIPING FROM METER TO BLDG (ONLY)
4) TEST NOT HOLDING