Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - CABLE DROP
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/10/2012 | ELECTRIC - CABLE DROP | Approved | PER EL FINAL | |
| 11/15/2011 | ELECTRIC - CABLE DROP | Partial Approval | IVRS - Inspection :* | |
| 11/07/2011 | ELECTRIC - CABLE DROP | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 11/03/2011 | ELECTRIC - CABLE DROP | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 10/21/2011 | ELECTRIC - CABLE DROP | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) ONLY ONE CONDUCTOR TO LUG TERMINATION 2) GROUNDING ELECTRODE CONDUCTOR TO TERMINATE AT GROUNDED TERMINAL 3) REDUCING WASHERS INSTALLED BACKWARDS 4) EQUIPMENT RATED AT 10,000 AIC PLANS STILL CALL FOR 22,000 AIC 5) A REFEE MAY BE ASSESED PER LAST INSPECTION NOTE |
|
| 08/11/2011 | ELECTRIC - CABLE DROP | Not ready for Inspection | IVRS - Inspection :* | |
| 08/05/2011 | ELECTRIC - CABLE DROP | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 06/29/2011 | ELECTRIC - CABLE DROP | Denied | IVRS - Inspection : See detailed listing on site.| 999* |