Permit: T09CM01205

Parcel: 13707044A


Addresses:

5201 S 12TH AV


Inspection Status: Approved

Inspection History: ELECTRIC - CABLE DROP

Permit Number - T09CM01205

Inspection Description - ELECTRIC - CABLE DROP

Inspection Status - Approved

Date Description Inspector Results Comments
01/10/2012 ELECTRIC - CABLE DROP Approved PER EL FINAL
11/15/2011 ELECTRIC - CABLE DROP Partial Approval IVRS - Inspection :*
11/07/2011 ELECTRIC - CABLE DROP Denied IVRS - Inspection :
See detailed listing on site.| 999*
11/03/2011 ELECTRIC - CABLE DROP Denied IVRS - Inspection :
See detailed listing on site.| 999*
10/21/2011 ELECTRIC - CABLE DROP Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) ONLY ONE CONDUCTOR TO LUG TERMINATION
2) GROUNDING ELECTRODE CONDUCTOR TO TERMINATE AT GROUNDED TERMINAL
3) REDUCING WASHERS INSTALLED BACKWARDS
4) EQUIPMENT RATED AT 10,000 AIC PLANS STILL CALL FOR 22,000 AIC
5) A REFEE MAY BE ASSESED PER LAST INSPECTION NOTE
08/11/2011 ELECTRIC - CABLE DROP Not ready for Inspection IVRS - Inspection :*
08/05/2011 ELECTRIC - CABLE DROP Denied IVRS - Inspection :
See detailed listing on site.| 999*
06/29/2011 ELECTRIC - CABLE DROP Denied IVRS - Inspection :
See detailed listing on site.| 999*