Permit: T09CM01198

Parcel: 140420200

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
07/31/2009 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
07/29/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
07/28/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) BOND TRANSFORMERS 250.24 AND 250.32
2) INSTALL GROUNDING ELECTRODE PER 250.64 (E)
3) DO NOT DBL STACK LUGS
4) INSTALL BUSHING ON TO THREADS
5) LABEL EQUIPMENT
ROOF:
1) DBL STARED LUGS
2) ONLY ONE CONDUCTOR PER LUG
3) BOND TRANSFORMER
4) LABEL EQUIPMENT
5) BOND CU-1 DISCONNECT
6) MISSING KO PLUG
7) EXPOSED CONDUCTORS IN EXHAUST FAN
8) OK ROOMS 101,109, BREAK, 111-114 EXCEPT CAMERAS ABOVE CEILING
07/22/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
07/17/2009 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
07/17/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) RECEIVED CHECK #002624 FOR $150.00
2) NOTE: BONDING IN CT CAN, NOT PER 250.102 AND 250.66
3) OK TO MAIN LUGS PANEL L1
4) DEVICES OK
5) NOTE: ABOVE CEILING WAS ROOM 110
07/15/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK SERVICE ITEMS
2) OK 2 X 4 LIGHTS AND CONDUIT
3) SUPPORT VDV CABELING 725.24, 800.24 & 300.11
4) FINISH EM LIGHTING AND POWER POLES
07/14/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
SERVICE:
1) BOND BUSHINGS AT CONCENTRICS 250.97
2) BOND ALL SERVICE RACEWAYS 250.92
3) NEED REJECTION PINS
INTERIOR:
1) DO NOT WRAP FLEX WHIPS AROUND CONDUIT CREATING A COIL
07/07/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) DISCUSSED PANEL CLEARANCES
2) SUPPORT VDV CABELING PER 725.24, 800.24, 392 AND 300.11
06/23/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WALLS & LIDS 105-108
06/19/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK WALLS 102-104, 108 & 109
2) OK COLUMN ROOM 110
06/18/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK EXTERIOR WALLS 104, 102 & 103
2) OK ROOMS 101,113,114, LOBBY OF 110
06/12/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WALL 111, 112 & EXTERIOR OF 110