Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/22/2010 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 12/16/2009 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) SUSPENDED ROUGH DUCT OK TO PROCEED 2) WHERE YOU INSTALL CEILING DIFFUSERS BE SURE TO PROVIDE A BEADED COLLAR ON EACH ONE FOR A FLEX DUCT/PANDUIT STRAP CONNECTION 3) CONDENSATE DRAINS OK 4) OK ON FINAL BE SURE EXHAUST FANS ARE ON A TIME CLOCK TO OPERATE THE ENTIRE TIME THE BLDG IS OCCUPIED |
|
| 12/15/2009 | MECHANICAL - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* |