Permit: T09CM01196

Parcel: 122183910


Addresses:

3552 E WILLARD ST


Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T09CM01196

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
09/24/2009 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
07/23/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) SEE NOTES 3550
07/21/2009 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) OUTSIDE USE ROMEX CONNECTOR AT TERMINATIONS INTO BOXES, SUPPORT EMT PER CODE, LOOSE FITTINGS-MUST BE WRENCH TITE PER CODE. UNIT LOCKED, PLANS/PERMIT ?