Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - PROGRESS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/14/2009 | ELECTRIC - PROGRESS | Approved | IVRS - Inspection :* | |
| 12/07/2009 | ELECTRIC - PROGRESS | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) DISCONNECTING MEANS FOR INSTA HOT 2) BOXES MORE THAN 1/4" 314.20 USE APPROVED PARTS 3) VERIFY SEPERATION FOR WIRING IN FLOOR BOX AND CLEAN EXCESS DIRT AND FOREIGN MATERIAL FROM BOX 4) BREAKERS NOT MARK CORRECTLY-ALSO LABEL PER 408.4 5) DISCONNECT NOT TO BE HORIZONTAL 6) PROPERLY TERMINATE EQUIPMENT GROUND CONDUCTOR 7) RECEPT IN INDUCTRIAL COVERS NOT PER CODE 8) FIXTURES NEED DISCONNECTING MEANS 410.63 9) PROPERLY LABEL CONDENSING UNITS |
|
| 11/09/2009 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* | |
| 11/03/2009 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* 1) OK BORDER CUTS ONLY |
|
| 10/07/2009 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* | |
| 10/05/2009 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* | |
| 09/16/2009 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* |