Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/31/2009 | ELECTRIC - FINAL | Approved | ||
| 07/31/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) ELECTRIC INSTALLATION AS PER NEC. FINAL SUBJECT TO APPROVAL FROM L. HANLY FOR UNLISTED EQUIPMENT |
|
| 07/22/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) NEED ELECTRICAL PLAN FOR POWER TO EQUIPMENT 2) ROOF A/C DISCONNECTS PER 250.97-NEED BOND BUSHINGS |
|
| 07/20/2009 | ELECTRIC - FINAL | Not ready for Inspection | THE EQUIPMENT AT THIS FACILITY MADE BY THE FOLLOWING COMPANIES---DEK, UNIVERSAL INSTRUMENTS, ELECTROVERT, CAMALOT--- HAS BEEN ACCEPTED BY THE BUILDING OFFICIAL AS MEETING THE REQUIREMENTS OF NEC 110.3 (A). THE ELECTRICAL INSPECTOR SHALL STOP HIS INSPECTION AT THE OUTLET WHERE THE MACHINES ARE CONNECTED. OBVIOUS HAZARDOUS CONDITIONS SUCH AS SUBSTANDARD WIRING METHODS FROM THE MACHINE TO THE FIRST OUTLET SHOULD BE BROUGHT TO THE ATTENTION OF THE BUILDING OFFICIAL. |
|
| 06/30/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PLEASE HAVE ELECTRICIAN PRESENT TO OPEN ELECTRICAL EQUIPMENT 2) MAINTAIN WORKING CLEARANCES AT PANEL '22' 110.26 3) PANEL LABELING TO BE PER 408.4 4) TIGHTEN LOOSE FITTINGS 5) FINISH PREVIOUS ITEM |