Inspection History: PLUMBING - GAS PRESSURE TEST

Permit Number - T09CM01144

Inspection Description - PLUMBING - GAS PRESSURE TEST

Inspection Status - Approved

Date Description Inspector Results Comments
06/24/2009 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection :*
06/11/2009 PLUMBING - GAS PRESSURE TEST Partial Approval IVRS - Inspection :*
FROM METER LOCATION THRU SYSTEM TO CAPS AT APPLIANCES OK

1. PROVIDE CORRECT SUPPORT FOR ROOFTOP PIPING
2. PROVIDE ANOTHER TEST TO APPLIANCE SHUT OFF VALVES
06/08/2009 PLUMBING - GAS PRESSURE TEST Not ready for Inspection IVRS - Inspection :*
1. PROVIDE MINIMUM 10 PSI TEST AT TIME OF INSPECTION
2. CHECK YOUR TEST GAUGE, IT APPEARS TO BE DEFECTIVE
3. PROVIDE ACCESS TO ROOFTOP
05/29/2009 PLUMBING - GAS PRESSURE TEST Not ready for Inspection IVRS - Inspection :*
05/28/2009 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. REMOVE FUTURE CONNECTIONS AT METER MANIFOLD OR REVISE PLAN (WHERE IS PLAN 2?)
2. NOTE: YOU WILL NEED TO CONTACT S.W. GAS FOR YOUR METER REQUIREMENTS
3. PROVIDE ACCESS TO 2" GAS SYSTEM TIED INTO NEW METER MANIFOLD