Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/01/2009 | PLUMBING - ROUGH, SOIL | Approved | IVRS - Inspection :* WATER TEST DWV FROM EXISTING PER PLAN THRU ROOF |
|
| 05/29/2009 | PLUMBING - ROUGH, SOIL | Not ready for Inspection | IVRS - Inspection :* | |
| 05/28/2009 | PLUMBING - ROUGH, SOIL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. REMOVE ALL WATER & WET SOIL & PROVIDE DRY FIRM BEDDING FOR PIPING 2. VENT FOR 4" P-TRAP TO BE INSTALLED PER 2006 UPC 3. TAILPIECE LENGTH TO BE MAXIMUM 24" IN LENGTH FROM FIXTURE TO TRAP WEIR 4. PROVIDE MINIMUM 10' HEAD TEST OR TEST THRU ROOF 5. EXPOSE CONNECTION TO EXISTING BUILDING DRAIN |