Permit: T09CM01144

Parcel: 11516025A

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T09CM01144

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
07/10/2009 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
06/25/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
06/11/2009 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
RECEIVED LETTER FOR OUTLET FROM ARCH.
06/01/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK 1/2" PVC U.G.
05/29/2009 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
05/28/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. USE BOX OFFSETS OR BENDS AS NEEDED IN CONDUIT RUNS DO NOT USE COUPLINGS TO MAKE BENDS
2. SUPPORT EMT WITHIN 3' OF BOX OR TERM. AND AT 10' MAX INTERVALS
05/27/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
PROVIDE LETTER FOR DELETION OF RECEPTACLE FROM ARCH.