Permit: T09CM01139

Parcel: 10603019B

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
06/11/2009 FRAMING Approved IVRS - Inspection :*
05/15/2009 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NEED GFI RECEPTACLES AT BATH AND KITCHEN COUNTER SPACE OR LOOPED TO A PROTECTED GFI CIRCUIT
2) STAIRS-HANDRAIL MUST TERMINATE AT LAST STEP
3) STEP AT ENTRY NEEDS TO HAVE MORE TRAVEL
4) KITCHEN RECEPTS HAVE OPEN GROUNDS
5) FURNACE IS GAS AND TAKING AIR FROM BEDROOM
05/11/2009 FRAMING Cancelled CANCELLED PER HOMEOWNER RUDY GARCIA #409-0219