Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/10/2009 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
| 06/09/2009 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. PROVIDE LISTING, PROOF OF 1" AIR GAP OR CORRECT BACKFLOW PROTECTION FOR WATER TO PRO-CLEAN AT 3-COMP SINK - FOR CHEMICAL ADDITION |
|
| 06/08/2009 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. CALL IN ALL INSPECTIONS 2. PROVIDE LONG RADIUS FITTING FOR INTERCEPTOR VENT BELOW FLOOD RIM 3. VENT FROM INTERCEPTOR TO BE 1' FROM SIDE WALL OBSTRUCTION 4. PROVIDE LISTING FOR BACKFLOW PROTECTION FOR CHEMICAL ADDITION AT 3-COMP SINK OR (PROVIDE IT) OR PROOF OF 1" AIR GAP 5. CAULK FIXTURES AT WALL |