Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T09CM01121
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/13/2009 | ELECTRIC - INTERMEDIATE | Approved | BEFORE HOURS INSP, 12:30 AM REQUEST BY CONTRACTOR PAID $150.00 WITH CHECK #5080 12:30 AM CLEARANCE TO MAP ROOM OK TAP CONNECTIONS INTO SES ONLY |
|
| 08/10/2009 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : Work is not complete enough to inspect.| 950* 1) NO WORK PROGRESS-UNECESSARY INSPECTIONS MAY RESULT IN A REFEE |
|
| 08/05/2009 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) SECURE CONDUIT SUPPORTS AND BOXES TO WALL WITH PROPER ANCHORS 2) TIGHTEN LOOSE FITTINGS 3) #8 AND LARGER TO BE STRANDED 310.3 4) FINISH MAKE UP SERVICE DISCONNECT 5) INSTALL GROUNDING ELECTRODE CONDUCTOR PER 250.64 (E) 6) DISCONNECT TAPS-RECALL FOR INSPECTION OF EQUIPMENT BEFORE RECONNECTION 7) RECEIVED CHECK #5079 FOR $150.00 |
|
| 08/05/2009 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* |