Permit: T09CM01121

Parcel: 11522002A


Addresses:

1390 W SPEEDWAY BL

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
08/13/2009 ELECTRIC - INTERMEDIATE Approved BEFORE HOURS INSP, 12:30 AM REQUEST BY CONTRACTOR
PAID $150.00 WITH CHECK #5080
12:30 AM CLEARANCE TO MAP ROOM
OK TAP CONNECTIONS INTO SES ONLY
08/10/2009 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
Work is not complete enough to inspect.| 950*
1) NO WORK PROGRESS-UNECESSARY INSPECTIONS MAY RESULT IN A REFEE
08/05/2009 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) SECURE CONDUIT SUPPORTS AND BOXES TO WALL WITH PROPER ANCHORS
2) TIGHTEN LOOSE FITTINGS
3) #8 AND LARGER TO BE STRANDED 310.3
4) FINISH MAKE UP SERVICE DISCONNECT
5) INSTALL GROUNDING ELECTRODE CONDUCTOR PER 250.64 (E)
6) DISCONNECT TAPS-RECALL FOR INSPECTION OF EQUIPMENT BEFORE RECONNECTION
7) RECEIVED CHECK #5079 FOR $150.00
08/05/2009 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*