Permit: T09CM01103

Parcel: 134251340


Addresses:

1114 S DUQUESNE DR

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Date Description Inspector Results Comments
08/26/2009 BUILDING - FINAL Approved IVRS - Inspection :*
08/25/2009 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) TPR MUST BE 3/4" METAL DRAIN TO 6" OF PAN
2) SECURE FLUE, CHANGE PITCH AND CHANGE VALVES
3) LABEL BREAKERS, CHANGE WATER PVC TO METAL
4) ADD BUBBLE COVERS ON GFI
5) CHANGE 2 WIRE OUTLETS TO 2 PRONG OR GFI'S