Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/15/2009 | MECHANICAL - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 06/12/2009 | MECHANICAL - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 06/08/2009 | MECHANICAL - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. A NEW DUCT SYSTEM WAS INSTALLED AND NOT ON PLANS 2. INSULATE ALL SHEETMETAL DUCT AND FITTINGS WITH R8 INSULATION W/VAPOR BARRIER 3. ANY DUCT IN A VENTILATED ATTIC ABOVE ATTIC INSULATION REQUIRES MIN. R8 - SEE SECTION 403 2006 IECC AND CITY AMMENDMENTS. 4. DO NOT USE A DRIVE CLEAT IN PLACE OF PLATE STRAP AT DRYER VENT 5. SCREW EXHAUST DUCT TO OUTLET ON EXHAUST FAN 6. PROVIDE R8 DUCT LINER IN EXPOSED DUCT ON ROOF 7. EXTEND WATER HEATER VENT MIN. 3' ABOVE COMBUSTION AIR INTAKE 8. SECURE AT CEILING 9. PAINT EXPOSED PVC ON ROOF W/LATEX PAINT 10. EXTEND COMBUSTION AIR VENT DOWN INTO WALL AND SEPARATE 11. PROVIDE 1/8" PER FT. SLOPE ON HORIZONTAL SECTION OF CONDENSATE DRAIN |