Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/16/2009 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 06/15/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) COMPLETE SMOKE ALARMS IN APPROVED BOXES 2) RELOCATE MASTER JUNCTION |
|
| 06/12/2009 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. ALL WORK TO CODE 2. SUBMIT ELEC. PLAN, PLUMBING PLAN - ALL WORK DONE 3. INSTALL HARD-WIRED SMOKE ALARMS BEDROOMS AND HALLWAYS 4. ACCESS PANELS FOR JUNCTION BOXES - MASTER CLOSET 5. BOND GAS LINE |
|
| 06/08/2009 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. BOX OVERFILLED 2. PLEASE PROVIDE GROUND TAILS FOR SWITCHES 3. PROTECT CONDUCTOR FROM SCREWS INSIDE OF BOXES 4. SECURE BOX IN WALL 5. PROTECT M/C CABLE IN SHALLOW CHANNEL 6. USE APPROVED BOX WITH M/C CABLE 7. SUPPORT M/C WITHIN 12" OF BOX 8. SUPPORT NM CABLE WITHIN 12" OF CANS & EXHAUST FANS AND BOXES 9. CABLES TO BE CLAMPED OR SECURED TO BOXES (ALL) 10. EXPOSED NM CABLE BACK PORCH 11. PROVIDE OUTLETS PER 210.52 12. PROVIDE LIGHT OUTLETS PER 210.70 13. MAKE UP ALL BOXES 14. WHERE ARE SMOKE DETECTORS 15. PROTECT CABLES FROM SHARP METAL EDGES OF CONDUITS 16. JUNCTION BOXES TO BE ACCESSIBLE 17. UNCOVER UNDERGROUND TO INSPECT 18. GROUND METAL JUNCTION BOXES |