Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T09CM01076
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/17/2009 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
07/15/2009 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) CALL IN ALL PLUMBING INSPECTIONS ON ACTIVITY CARD THAT HAVE NOT BEEN APPROVED 2) READ NOTES FROM 6/18/09 INSPECTION, EXPOSE CLOSET FLANGES AND PROVIDE ACCESS TO 1ST LEVEL CEILING SPACE 3) TURN ON WATER TO TRAP PRIMERS 4) PROVIDE EXPANSION TANK FOR WATER HEATER PROPERLY SUPPORTED 5) PROVIDE MININMUM 6" CRITICAL LEVEL FOR URINAL FLUSH VALVES 6) MAKE JANITOR SINK WATER TIGHT IN NORTH WEST CORNER |