Permit: T09CM01069

Parcel: 10408076F


Addresses:

4405 N ORACLE RD


Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T09CM01069

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
08/07/2009 MECHANICAL - FINAL Approved OK FOR FINAL
TESTED DUCT SMOKE DETECTORS
COLLECTED $150.00 MONEY ORDER FOR AFTER HOURS INSPECTION
08/06/2009 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1) PROVIDE AUDIBLE AND VISIBLE ALARMS FOR DCUT SMOKE DETECTORS
2) SUPPORT FLEX DUCTS 5' INTERVALS
3) SECURE REFER LINES IN ATTIC
4) OK TO WRAP FITTINGS IN ATTIC
5) PROVIDE AIR BALANCE REPORT
6) MARK UNIT DATA PLATES
7) ID UNITS
8) BLUE REFER LINE INSULATION SEAMS AND JOINTS
9) FINISH CONDENSATE TO MINI SPLIT
10) TERMINATE CONDENSATE TO AN APPROVED LOCATION