Permit: T09CM01067

Parcel: 12620001C

Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Permit Number - T09CM01067

Inspection Description - PLUMBING - ROUGH, SOIL

Inspection Status - Approved

Date Description Inspector Results Comments
06/08/2009 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection :*
05/11/2009 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
WATER TEST UNDERGROUND THRU REVENT OK
1. NEED TO SEE CORRECT INTERCEPTOR INSTALL WITH TEST
05/08/2009 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
WATER TEST FROM POINT OF CONNECTION AT 4" BLD. DRAIN THRU 4" UPPER TERMINAL (FLO) 3" CONTINUES FOR RELOCATED SINK, FLOOR SINK AND 3-COMP SINK WITH INTERMEDIATE C/O's

1. PROVIDE 2" FLOOR SINK SOLVENT WELD P-TRAP WITH RETEST