Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - PROGRESS
Permit Number - T09CM01041
Inspection Description - ELECTRIC - PROGRESS
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/17/2010 | ELECTRIC - PROGRESS | Approved | ||
10/07/2010 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* 1) OK MEMBERSHIP GRID/OK EXIT VESTIBLE HARD LID |
|
10/06/2010 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* 1) J-BOXES NEED TO BE ACCESSIBLE IN HAR LID N.E. EXIT 2) J-BOX OR MOTOR STARTER NEEDS WORKING CLEARANCE PER 110.26 NEC, MEMBERSHIP 3) REMOVE LV. CABLING NOT BEING USED |
|
10/01/2010 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* 1) OK LIGHT SWITCH ROUGH FOR STORAGE ROOM AT FRONT OF STORE |
|
09/29/2010 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* 1) OK WALLS MEMBERSHIP |
|
09/22/2010 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* 1) OK ABOVE CEILING NEW DEMO ROOM AND ROTISSORIE |
|
09/17/2010 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* 1) OK FINAL FOR DELI ROOM AND DEMO ROOM |
|
09/09/2010 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* 1) OK WALL ROUGH ROTISSERIE |
|
08/31/2010 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* 1) OK COMPLETE FOR MAINT, JANITOR, ASSOC. RESTROOM AND PRODUCE PREP |
|
08/18/2010 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* OK ROUGH WALL IN MEAT PREP |
|
08/16/2010 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* OK MAINT & JANITOR CLOSET WALLS ROUGH, PRODUCE PREP |
|
07/29/2010 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* 1) OK RESTROOM ROUGH AT TIRE SHOP |
|
07/15/2010 | ELECTRIC - PROGRESS | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
07/14/2010 | ELECTRIC - PROGRESS | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) FLEX USED AS FIXTURE WHIPS LONGER THAN 6' NEED TO BE SUPPORTED PER NEC 2) HAVE OPEN J-BOXES, FLEX WITH CONDUCTORS HANGING DOWN BELOW GRID ?? 3) THIS INSPECTION IS FOR THE OLD BAKERY AREA |
|
07/08/2010 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* 1) OK ROUGH, WALLS AND HARD LID IN RECORDS ROOM |
|
07/01/2010 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* 1) OK ABOVE CEILINGS, CAFE, TRAINING ROOM AND BAKERY |
|
06/21/2010 | ELECTRIC - PROGRESS | Denied | 1) FIXTURES (GRID) MUST BE SECURED TO GRID | |
06/17/2010 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* 1) OK ABOVE CEILING EXCEPT TRAINING ROOM |
|
06/03/2010 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* 1) OK NEW WALL AT TRAINING ROOM MEZZ. |
|
05/25/2010 | ELECTRIC - PROGRESS | Not ready for Inspection | IVRS - Inspection :* | |
05/18/2010 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* OK FORK LIFT BATTERY CHARGER RELOCATION |