Permit: T09CM01029

Parcel: 13216592C


Addresses:

1740 E FAIR ST

Inspection Status: Approved

Inspection History: ELECTRIC - UNDERGROUND

Date Description Inspector Results Comments
08/31/2009 ELECTRIC - UNDERGROUND Approved IVRS - Inspection :*
08/25/2009 ELECTRIC - UNDERGROUND Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) SECURE RISER TO STRUCTURE
2) PLEASE EXPOSE GROUND RODS
3) PROTECT CONDUCTORS 352.46 & 300.4
4) INSTALL MAIN BONDING JUMPER
5) LABEL SERVICE DISCONNECT AND BREAKER
6) FILL UNUSED OPENINGS IN BOTTOM OF SUB PANEL
7) ONLY ONE GROUNDED CONDUCTOR TO TERMINAL LUG