Permit: T09CM01016

Parcel: 117160070


Addresses:

191 E TOOLE AV


Inspection Status: Approved

Inspection History: FIRE - FINAL

Permit Number - T09CM01016

Inspection Description - FIRE - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
10/28/2009 FIRE - FINAL Approved
08/06/2009 FIRE - FINAL Denied 1.) Need to label door leading down to basement,"BASEMENT" and "RISER ROOM". 4 in. high letters ninimum.
2.) Need to also label door located in the basement leading into room where the sprinkler riser is located,"RISER ROOM".
3.) Need to readily access the room to the sprinkler riser without the use of a key.
4.) Missing a sprinkler wrentch from the spare box.
5.) Need to remove slide bolts and cross-bar locking devices from the rear double doors and replace with thumb-turn locks or panic hardware.
6.) Must provide an inspection report from an engineer indicating that the broken floor joists (seen from below in the basement area) have been repaired and that the rest of the floor has been inspected and approved.
6.) Need current annual sprinkler report.
7.) Need current 5 year check valve inspection report.