Inspection Status: Denied
Inspection History: MECHANICAL - FINAL
Permit Number - T09CM00948
Inspection Description - MECHANICAL - FINAL
Inspection Status - Denied
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/03/2009 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. ALL ROOFTOP DUCT AND DUCT EXPOSED TO EXTERIOR TO HAVE A MINIMUM OF R-8 (2") 2. TWO UNITS ON ROOF INSTALLED WITHOUT PERMITS, MANUF. DATES OF 4/08 AND 7/08, PROVIDE PERMIT PRIOR TO THIS FINAL 3. PROVIDE SERVICE OUTLETS (GFI) WITHIN 25' OF EQUIPMENT |
|
08/13/2009 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) DUCT SMOKE DETECTORS NOT TIED TO ALARM SYSTEM |
|
08/12/2009 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
08/04/2009 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1) COMPLETE DUCT SMOKE DETECTORS (X3) 2) TERMINATE CONDENSATE IN AN APPROVED LOCATION 3) PROVIDE SMOKE FOR TESTING |