Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/30/2009 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 05/27/2009 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK TO SHEETROCK OFFICE |
|
| 05/20/2009 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* ATTIC INSULATION IN PLENUM CEILINGS MUST BE PLENUM RATED OR PROVIDE A PLENUM RATED COVERING. THIS INCLUDES ALL AREAS COMMUNICATING WITH THE SAME PLENUM. ALSO, PROVIDE A DUCT SMOKE DETECTION SYSTEM IF PLENUM EXCEEDS 2000 CFM |