Permit: T09CM00924

Parcel: 138110390


Addresses:

6250 S FONTANA AV

Inspection Status: Approved

Inspection History: EXT METAL CLIPS/EXT SHEATHING

Date Description Inspector Results Comments
05/05/2010 EXT METAL CLIPS/EXT SHEATHING Approved IVRS - Inspection :*
05/04/2010 EXT METAL CLIPS/EXT SHEATHING Not ready for Inspection IVRS - Inspection :*
01/07/2010 EXT METAL CLIPS/EXT SHEATHING Partial Approval IVRS - Inspection :*
1) NO PVC H20 LINES INSIDE HOUSE
2) NO SCREEN ON DRYER T-TOP
3) APPROVED FAN BOXES
4) SEE INSPECTION REF H.D.'S
5) TWO 20 AMP COUNTER TOP CIRCUITS 12" FROM OPENING 4'-0" ON CENTER
6) RE-VENT 6" ABOVE KIT SINK OR USE 45 DEGREE
12/24/2009 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PROVIDE SAFE ACCESS TO ROOF
2) NO PLANS FOUND
3) INTERMEDIATE INSPECTIONS NOT DONE UNTIL LATHE IS COMPLETE
4) DO NOT LATHE UNTIL 1030 & 1025 ARE APPROVED
5) DO NOT SHEETROCK
6) REMOVE INSULATION FOR INSPECTION