Permit: T09CM00917

Parcel: 117050020


Addresses:

400 N 2ND AV


Inspection Status: Approved

Inspection History: PLUMBING - ROOF DRAINS

Permit Number - T09CM00917

Inspection Description - PLUMBING - ROOF DRAINS

Inspection Status - Approved

Date Description Inspector Results Comments
01/06/2011 PLUMBING - ROOF DRAINS Approved
12/29/2010 PLUMBING - ROOF DRAINS Partial Approval IVRS - Inspection :*
1) APPROVAL OF RAINWATER LEADERS SUBJECT TO APPROVAL OF REDUCTION FROM 10" TO 8" AT EXTERIOR OF BLDG. MUST BE STAMPED BY BOB SHERRY
2) OK TO COVER
12/28/2010 PLUMBING - ROOF DRAINS Not ready for Inspection IVRS - Inspection :*
1. I SEE NO EVIDENCE OF BEDDING OF UPPER OR LOWER ENDS OF PIPE
2. I SEE NO CORRECTIONS OF THE MANHOLE
3. I SEE NO VERIFICATION OF TESTING OF PIPE OR MANHOLE
4. I DON'T SEE A TRACER
5. NO VERIFICATION OF GRADE
12/23/2010 PLUMBING - ROOF DRAINS Not ready for Inspection IVRS - Inspection :*
12/15/2010 PLUMBING - ROOF DRAINS Partial Approval IVRS - Inspection :*
11/12/2009 PLUMBING - ROOF DRAINS Partial Approval IVRS - Inspection :*
1) 8" RWL FROM 2ND LEVEL DRAIN BODIES THRU 10" TO BLDG EXTERIOR NORTH AND SOUTH LOCATION WATER TEST OK
2) 2"FOR FLOOR SINK PER PLAN TO BLDG EXTERIOR WATER TEST OK