Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T09CM00911

Parcel: 10602248A


Addresses:

3710 N ORACLE RD


Inspection Status: Approved

Inspection History: FIRE - FINAL

Permit Number - T09CM00911

Inspection Description - FIRE - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
05/20/2009 FIRE - FINAL Approved
04/20/2009 FIRE - FINAL Denied 1. IFC 3809.12 Clear all combustibles 10 feet away from LP tanks.
2. Install "NO SMOKING" signs by LP Tanks - no smoking within 10 feet.
3. Remove slide bolt locks and double cylinder keyed dead bolt lock from exit in bar, only panic hardware is allowed on the door.
4. In patio area east exit gate needs panic hardware and install Illuminated exit sign by gate.
5. Need permit for the installation of permanent canopy. Can not use canopy pole type that is held down with 55 gal drums.