Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/04/2009 | FRAMING | Approved | IVRS - Inspection :* 1) TAPE CONDUCTOR ENDS 220 2) RAISED LETTER ADDRESS METAL METER BASE |
|
| 12/01/2009 | FRAMING | Partial Approval | IVRS - Inspection :* 1) PENDING ALL TRADES 2) PROVIDE GAS BOND 3) OK TO INSULATE |
|
| 11/12/2009 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) BLOCK REGISTER BOOTS 3 SIDES 2) NAIL PROTECT ELECTRICAL THROUGHOUT 1 1/4" STUDS EDGE 3) SECURE ROMEX 8" FROM BOXES THROUGHOUT 4) 12-2 CIRCUITS REQUIRED IN KITCHEN PER PLAN 5) 2" VTR AT KITCHEN SINK OR SUBMIT AS BUILT 6) MISSING SMOKE ALARMS 7) TERMINATE ROMEX PROPERLY INTO EXHAUST FANS 8) INSTALL #8 TO HEAT PUMP WITH 12-2 SERVICE 110 9) 12-2 ALL EXT GFCI MISSING REAR PORCH AND BATH OUTLETS 10) MANY JUNCTION BOXES IN ATTIC, REVISE PLAN OR WIRE TO PLAN 11) PANEL NOT GROUNDED/NO RISER/20 AMP CIRCUITS 14 GAUGE WIRING/NO METER BASE/SEAL OPENINGS/NOT PER CODE 12) MISSING CLIPS 3 POINT BEARING TRUSSES ENTRY, PROVIDE TRUSS CALCS |
|
| 10/13/2009 | FRAMING | Not ready for Inspection | IVRS - Inspection :* 1) COMPLETE ALL TRADES PRIOR TO FRAME INSPECTION |