Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/01/2010 | ELECTRIC - FINAL | Approved | ||
| 07/23/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PLANS NOT STAMPED OR APPROVED |
|
| 06/04/2009 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* NEED APPROVED REVISED PLANS FOR SITE LOCATIONS |
|
| 06/03/2009 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* CANCELED |
|
| 06/02/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. CANNOT TRIM CONDUCTORS TO FIT 2. LABEL EQUIPMENT 3. NEED REVISED PLANS STAMPED AND APPROVED |
|
| 05/18/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. BOND JUMPER TO BE PER 250.102 2. ONLY ONE CONDUCTOR PER LUG 3. NEED REJECTION PINS 4. NEUTRAL NEEDED AT SERVICE DISCONNECT 250.24 (C) 5. INSTALL MAIN BONDING JUMPER AT TRANSFORMER 6. PLEASE REVISE PLANS TO SHOW EMON METER & NEUTRALS 7. PROTECT CONDUCTORS AT FITTING -- 300.4 |