Permit: T09CM00841

Parcel: 13606002C


Addresses:

8800 E 22ND ST 02


Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T09CM00841

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
11/09/2009 PLUMBING - FINAL Approved IVRS - Inspection :*
11/06/2009 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1) CONTRACTOR CANCELLED BY MIKE
11/05/2009 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
1) RECEIVED LETTER GLUEING OK FOR WATER VALVES, WOOD ROOF SUPPORTS FOR GAS PIPING
2) TRISOLATORS ARE REQUIRED AND WILL BE INSTALLED PROPERLY TOMORROW PER NOTE #11 FROM 10/30/09 INSPECTION
3) WOOD BLOCKS ON ROOF NEED TO BE IN CONTACT WITH ROOF, SECURED AND CORRECT INTERVALS PER NOTE #12 10/30/09 AND NOTE #1 11/02/09. WATER HAMMER APPEARS TO BE A FIXTURE WARRANTY ISSUE WAITING TO BE CORRECTED
4) NEED CERTS FOR BACKFLOWS AS REQUESTED PER NOTE #16 & 17 10/30/09, NEED DOCUMENTATION FOR ACCEPTANCE OF CONDITIONS OF LETTER FOR SPEC CHANGES FROM ADAMS & ASSOCIATES (ENGINEER) FROM CONTRACTOR AND OWNER
11/04/2009 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1) CONTRACTOR CANCELLED BY MIKE
11/03/2009 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1) CONTRACTOR CANCELLED BY MIKE
11/02/2009 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1) PROVIDE CORRECT SUPPORTS FOR ROOF TOP GAS PIPING
2) PROVIDE ACCESS TO WATER VALVES IN RESTROOMS
3) PROVIDE PROOF OF WATER HAMMER ARRESTOR AND RELIEVE WATER HAMMER SHOCK IN RESTROOMS
4) PROVIDE LETTER FROM ENGINEER GIVING OK FOR WOOD SUPPORTS FOR ROOF TOP GAS PIPING
5) HAVE HOT WATER ON TO ALL FIXTURES
6) HOW WILL YOU ACCESS FOR SERVICE TEMPERING VALVES FOR SHOWERS ?
10/30/2009 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
1) PARTIAL GIVEN FOR TCO PURPOSE ONLY
2) LIST MAY NOT BE COMPLETE
3) COURTESY INSPECTION PROVIDED
4) STERILIZATION OK
5) ALL FIXTURES ARE WORKING
6) PLUMBING HAS NO PROBLEM WITH TCO
7) CONTRACTOR SHALL PROVIDE ACCESS TO ALL AREAS REQUIRING RE-INSPECTIONS
8) SEVERAL CHANGES FROM THE PLAN SPECS HAVE BEEN MADE
9) NO RED LINES OF DOCUMENTATION
10) BUTTERFLY VALVES FOR 2 1/2" DOMESTIC WATER
11) 15100 SEC 2.01 TRISOLATORS SEC 2.09 #6
12) SUPPORTS FOR ROOF TOP PIPING 2.09 B
13) WATER HAMMER AT URINAL FLUSHOMETERS
14) PROVIDE A PSI GAUGE
15) CORRECT RD SUPPORTS AND DRIP AT WOMEN'S LAV SUPPLY
16) I SEE NEW BACKFLOW INSTALL IN PROGRESS
17) INTERNAL ASSEMBLIES REQUIRE PDSD INSPECTION
18) ALSO YOU STILL HAVE AN UNLAWFULL CONNECTION AT RP WHICH PRESENTS A CONTAMINATION HAZARD FOR THIS OPERTING SCHOOL
10/29/2009 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1) CALL FOR AND HAVE ALL REQUIRED INSPECTIONS APPROVED PRIOR TO REQUESTING FINAL PLUMBING
2) RESOLVE ALL OUTSTANDING ISSUES (COMPLETE THE WORK)
3) A COURTESY WALK THRU WAS DONE; CORRECT LEAKS, INSULATE HW AND HWR PIPING