Permit: T09CM00825

Parcel: 10604023B

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T09CM00825

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
06/03/2009 ELECTRIC - FINAL Approved IVRS - Inspection :*
06/01/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
There is no access to the site.| 920*
OFFICE LOCKED
CALL BACK FOR REINSPECTION
05/29/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
SEE NOTES FOR CABLE CONN.
05/15/2009 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
NEED ROMEX CONNECTOR FOR PANCAKE BOX
05/14/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
There is no access to the site.| 920*
1) RECALL INSPECTION OFFICE LOCKED
05/07/2009 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
COMPLETE ITEMS FROM 5/6/09
HAVE PREVIOUS INSPECTION REPORTS ON SITE
05/06/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1/4" CABLE SHEATH IN BOX -- USE APPROVED CABLE CONNECTOR, SCREWS
05/01/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) CALLED INTO OFFICE
2) CALL FOR FINAL AFTER POWER CHECK
04/30/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. IF YOU ARE GOING TO HANG CEILING FANS YOU MUST USE APPROVED FAN BOXES
2. OK ROUGH WALLS
04/29/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. SUPPORT ROMEX WITHIN 12" OF BOX
2. BOX ON SOUTH WALL OVERFILLED - USE DBL. GANG BOX
3. OUTSIDE LIGHTS NEED TO BE SUPPORTED TO WALL, SUPPORT CONDUIT.