Permit: T09CM00812

Parcel: 13414001K

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
06/22/2009 MECHANICAL - FINAL Approved IVRS - Inspection :*
TESTED DUCT SMOKE DETECTORS
OK FOR FINAL
06/12/2009 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*
DEBUG INTERLOCK AND RECALL

ALL UNITS MUST SHUT DOWN WITH ANY SENSOR TRIP
06/10/2009 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
INTERLOCK DUCT SMOKE DETECTORS AND A/C UNITS