Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
Permit Number - T09CM00812
Inspection Description - MECHANICAL - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/18/2009 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* STILL NEED TO SEE DUCT SMOKE DETECTOR SYSTEM OK FOR CEILING TILES |
|
04/28/2009 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
04/21/2009 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1. OK FOR SCRIM PAPER IN PLENUM CEILING 2. THE RETURN PLENUM DOES NOT HAVE A DUCT SMOKE DETECTION SYSTEM. 3. PLENUM WELL EXCEEDS 2000 CFM OF RETURN AIR AND WILL NEED A SMOKE DETECTION SYSTEM 4. ALL UNITS SERVING THE PLENUM WILL NEED TO BE INTERLOCKED FOR FAN SHUT DOWN AND PROVIDE AN AUDIBLE AND VISIBLE ALARM. SEE SECTION 606.2.2 -- 2006 IMC |