Permit: T09CM00812

Parcel: 13414001K

Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Permit Number - T09CM00812

Inspection Description - MECHANICAL - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
05/18/2009 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
STILL NEED TO SEE DUCT SMOKE DETECTOR SYSTEM
OK FOR CEILING TILES
04/28/2009 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
04/21/2009 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1. OK FOR SCRIM PAPER IN PLENUM CEILING
2. THE RETURN PLENUM DOES NOT HAVE A DUCT SMOKE DETECTION SYSTEM.
3. PLENUM WELL EXCEEDS 2000 CFM OF RETURN AIR AND WILL NEED A SMOKE DETECTION SYSTEM
4. ALL UNITS SERVING THE PLENUM WILL NEED TO BE INTERLOCKED FOR FAN SHUT DOWN AND PROVIDE AN AUDIBLE AND VISIBLE ALARM.

SEE SECTION 606.2.2 -- 2006 IMC