Permit: T09CM00805

Parcel: 126162510


Addresses:

4002 E COOPER ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
05/22/2009 ELECTRIC - FINAL Approved IVRS - Inspection :*
ALL ITEMS HAVE BEEN CORRECTED
05/12/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. NEED PROPER WORKING CLEARANCES IN FRONT
OF PANEL @ WATER HEATER -- NEC 110.26
2. WAS NEW PANEL INSTALLED @ THIS LOCATION PART OF THIS PERMIT?
3. NEED BETTER COPY OF PLAN CANNOT BE READ
4. NEED PROPER WORKING CLEARANCES IN FRONT OF PV EQUIPMENT - NEC 110.26
5. EQUIPMENT TO BE OFF AND OPEN FOR INSPECTION
6. SEAL OPEN KNOCKOUT @ SERVICE PANEL
7. NEUTRAL TO TERMINATE IN LUG @ SERVICE PANEL WITH NO OTHER WIRES
8. PROPERLY INSTALL EMT ON ROOF PER NEC 358
9. NOT A COMPLETE INSPECTION