Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/22/2009 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* ALL ITEMS HAVE BEEN CORRECTED |
|
| 05/12/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. NEED PROPER WORKING CLEARANCES IN FRONT OF PANEL @ WATER HEATER -- NEC 110.26 2. WAS NEW PANEL INSTALLED @ THIS LOCATION PART OF THIS PERMIT? 3. NEED BETTER COPY OF PLAN CANNOT BE READ 4. NEED PROPER WORKING CLEARANCES IN FRONT OF PV EQUIPMENT - NEC 110.26 5. EQUIPMENT TO BE OFF AND OPEN FOR INSPECTION 6. SEAL OPEN KNOCKOUT @ SERVICE PANEL 7. NEUTRAL TO TERMINATE IN LUG @ SERVICE PANEL WITH NO OTHER WIRES 8. PROPERLY INSTALL EMT ON ROOF PER NEC 358 9. NOT A COMPLETE INSPECTION |