Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T09CM00801
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/21/2009 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
05/19/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. SWITCHES @ BACK ENTRANCE MIS-WIRED ONE SWITCH TURNS OFF ALL LIGHTS 2. NEED 22KAIC MAIN BREAKER PER SERIES LISTING. INSTALL BREAKER LISTED FOR USE IN PANEL 3. IS SINGLE POLE 30a 10KAIC RATED PER PLANS 4. MARK EQUIPMENT FOR SERVICE RATING PER NEC 110.22 5. ROOFTOP GFI NO POWER/NOT WORKING 6. USE LISTED NON-METALLIC SEAL TIGHT FITTINGS WITH NON-METALLIC SEAL TIGHT |