Permit: T09CM00801

Parcel: 12613018A


Addresses:

4578 E BROADWAY BL


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T09CM00801

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
05/21/2009 ELECTRIC - FINAL Approved IVRS - Inspection :*
05/19/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. SWITCHES @ BACK ENTRANCE MIS-WIRED ONE SWITCH TURNS OFF ALL LIGHTS
2. NEED 22KAIC MAIN BREAKER PER SERIES LISTING. INSTALL BREAKER LISTED FOR USE IN PANEL
3. IS SINGLE POLE 30a 10KAIC RATED PER PLANS
4. MARK EQUIPMENT FOR SERVICE RATING PER NEC 110.22
5. ROOFTOP GFI NO POWER/NOT WORKING
6. USE LISTED NON-METALLIC SEAL TIGHT FITTINGS WITH NON-METALLIC SEAL TIGHT