Permit: T09CM00797

Parcel: 132191120


Addresses:

2345 E IRVINGTON RD


Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Permit Number - T09CM00797

Inspection Description - MECHANICAL - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
12/29/2009 MECHANICAL - ABOVE CEILING Approved
12/22/2009 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
12/17/2009 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
12/16/2009 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) THE SECTIONS IF CONDENSATE PIPING ON ROOF THAT ARE PARALLEL TO THE ROOF EDGE DO NOT HAVE MIN. 1/8" PER FT. SLOPE
12/15/2009 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) WALK IN/ REACH IN CONDENSATE PIPING OK
12/07/2009 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) OK FOR TILES MECHANICAL ONLY
11/04/2009 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) OK TO PROCEED
10/29/2009 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) PROVIDE CONIAL TAPS PER PLANS
2) PROVIDE METAL GEAR TYPE BANDS ON FLEX DUCT PER PLANS
3) FLEX DUCT NOT TO EXCEED 8' PER PLANS
4) PROVIDE CLIPS AT WARD FLANGE CONNECTIONS
5) SEAL ALL LONGITUDINAL DUCT SEAMS PER PLANS (EXCLUDE PITSBURGH SEAMS)