Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
Permit Number - T09CM00797
Inspection Description - MECHANICAL - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/29/2009 | MECHANICAL - ABOVE CEILING | Approved | ||
12/22/2009 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
12/17/2009 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
12/16/2009 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) THE SECTIONS IF CONDENSATE PIPING ON ROOF THAT ARE PARALLEL TO THE ROOF EDGE DO NOT HAVE MIN. 1/8" PER FT. SLOPE |
|
12/15/2009 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) WALK IN/ REACH IN CONDENSATE PIPING OK |
|
12/07/2009 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) OK FOR TILES MECHANICAL ONLY |
|
11/04/2009 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) OK TO PROCEED |
|
10/29/2009 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) PROVIDE CONIAL TAPS PER PLANS 2) PROVIDE METAL GEAR TYPE BANDS ON FLEX DUCT PER PLANS 3) FLEX DUCT NOT TO EXCEED 8' PER PLANS 4) PROVIDE CLIPS AT WARD FLANGE CONNECTIONS 5) SEAL ALL LONGITUDINAL DUCT SEAMS PER PLANS (EXCLUDE PITSBURGH SEAMS) |